HomeMy WebLinkAboutDRAWINGS - Cornell - Carpenter Hall Renovations - STRC (2)1.CONCRETE SHALL BE AS FOLLOWS: STRENGTH MAX AGG AIR MAX W/C FOOTINGS 3000 PSI 1.5"NONE 0.5 INTERIOR SLABS 3500 PSI 1.5"NONE 0.5 EXTERIOR SLABS 5000 PSI 1.5"6%±1.5% 0.40 UNPROTECTED FOUNDATION WALLS 4500 PSI 3/4"6%±1.5%0.40 PIER 4500 PSI 3/4"6%±1.5%0.40 GRADE BEAMS 4000 PSI 3/4"NONE 0.45 2.ALL CONCRETE TO CONTAIN WATER REDUCING ADMIXTURE. 3.CEMENT TO BE TYPE 1 PORTLAND CEMENT. FLY ASH OR BLAST FURNACE SLAG SHALL BE USED IN COMBINATION WITH PORTLAND. 4.SEE SPECIFICATION FOR ADDITIONAL INFORMATION. 5.REINFORCING STEEL SHALL CONFORM TO ASTM A-615-60 GRADE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. 6.ALL REINFORCING STEEL SHALL HAVE CONCRETE COVER AS FOLLOWS: -CONCRETE CAST AGAINST FORMS 2" -CONCRETE CAST AGAINST EARTH 3" -SLABS -1.5" MIN 7.SEE REBAR LAP LENGTH SCHEDULE FOR BAR LAP LENGTHS. 8.CURE ALL EXPOSED CONCRETE USING SUPERVISED WET CURE OR AN APPROVED CURING COMPOUND. IF A CURING COMPOUND IS USED, PROVIDE CERTIFICATION THAT THE CURING COMPOUND IS COMPATIBLE WITH FLOOR COVERINGS AND ADHESIVES. 9.EXTERIOR ENTRY SLABS TO RECEIVE A LIGHT BROOM FINISH. TEXTURE TO BE APPROVED BY THE ARCHITECT OR OWNER'S REPRESENTATIVE. 10.PROVIDE ALL TIE BARS, SPACER BARS, CHAIRS AND ACCESSORIES. 11.VERIFY SIZE AND LOCATION OF ALL OPENINGS IN CONCRETE FOUNDATION WALLS AND FOOTINGS. 12.ALL PENETRATIONS THROUGH STRUCTURAL SLABS, WALLS, AND FOOTINGS SHALL BE SLEEVED OR CHASED. CORE-DRILLING OF SLABS, WALLS, AND FOOTINGS IS NOT PERMITTED. 13.INTERIOR SLAB FINISH TO BE HARDENED STEEL TROWEL FINISH. SEE ARCH DRAWINGS FOR FLOOR FINISHES 14.PROVIDE CONTRACTION JOINTS IN SLABS ON GRADE AS SHOWN . SEE SLAB ON GRADE DETAIL FOR JOINTING INSTRUCTIONS. SAW-CUT CONTRACTION-JOINTS WITHIN 4 HRS Of FINAL FINISH USING THE EARLY ENTRY DRY-CUT SAW METHOD. 15.ALL SAW-CUT & FORMED JOINTS IN SLAB ARE TO BE FILLED WITH A POLY-UREA BASED JOINT FILLER. ALLOW SLABS TO CURE 30 DAYS MIN BEFORE FILLING JOINTS. 16 FINE AND COURSE AGGREGATE FOR CONCRETE SHALL BE FROM AN APPROVED NYSDOT SOURCE AS LISTED ON THE NYSDOT WEBSITE WWW.DOT.NY.GOV IF THE AGGREGATE HAS THE POTENTIAL FOR ALKALI SILICA REACTION (ASR) AS INDICATED ON THE DOT WEBSITE, THE PORTLAND CEMENT USED IN THE MIX MUST BE LOW ALKALI (TOTAL ALKALI < 0.7%) OR THE MIX MUST INCLUDE 20% FLY ASH OR GGBFS. REINFORCED CONCRETE NOTES @..................AT ADD'L........ADDITIONAL ADJUS.......ADJUSTMENT ARCH.........ARCHITECTURAL OR ARCHITECT BCX...........BOTTOM CHORD EXTENTION B.O............BOTTOM OF BS.............BOTH SIDES OR BRICK SHELF BP.............BEARING PLATE BRG...........BEARING CL...............CENTER LINE CFMF.........COLD FORMED METAL FRAMING CJ.............CONTROL JOINT CMA..........COLUMN MASONRY ANCHOR CMU...........COLUMN MASONRY UNIT COL...........COLUMN CONT.........CONTINUOUS CONC.........CONCRETE DIA ............DIAMETER DO.............DITTO -REPEAT PREVIOUS DWG..........DRAWING DWGS........DRAWINGS E-W...........EAST-WEST OR EACH WAY EA.............EACH EC.............ELECTRICAL WORK PRIME CONTRACTOR ELEV.........ELEVATION EMBED.......EMBEDMENT EOD...........EDGE OF DECK EOJ...........END OF JOIST EOS...........EDGE OF SLAB EQ.............EQUAL ES.............EACH SIDE EXG...........EXISTING EXP...........EXPANSION EXT...........EXTERIOR FD.............FLOOR DRAIN FF..............FINISHED FLOOR FIN FLR.....FINISHED FLOOR FNDN.........FOUNDATION FS.............FOOTING STEP OR FAR SIDE FTG............FOOTING GA.............GAGE GALV.........GALVANIZED GC.............GENERAL TRADES PRIME CONTRACTOR H OR HOR... HORIZONTAL HC.............HVAC PRIME CONTRACTOR HP.............HIGH POINT INFO...........INFORMATION INT.............INTERIOR K................KIPS KB..............KNEE BRACE KSI.............KIPS PER SQUARE INCH L................ANGLE LLBB..........LONG LEG BACK-TO-BACK LLH............LONG LEG HORIZONTAL LLV............LONG LEG VERTICAL LMF............LIGHT GAGE METAL FRAMING MAX...........MAXIMUM MC.............MASONRY OPENING MIN............MINIMUM MECH.........MECHANICAL M.O............MASONRY OPENING N-S............NORTH-SOUTH NS..............NEAR SIDE NTS............NOT TO SCALE NYSBC........NEW YORK STATE BUILDING CODE O.C.............ON CENTER PL OR P....PLATE PC..............PLUMBING WORK PRIME CONTRACTOR PROJ..........PROJECT PSF............POUNDS PER SQUARE FOOT PSI.............POUNDS PER SQUARE INCH REINF.........REINFORCE REQ'D.........REQUIRED RD.............ROOF DRAIN SCHED........SCHEDULE SECT..........SECTION SF..............SQUARE FOOT SIM............SIMILAR SL..............SLOPED SLBB..........SHORT LEG BACK-TOBACK SPEC'S.......SPECIFICATIONS SQ.............SQUARE STD...........STANDARD T/..............TOP OF TBR...........TO BE REMOVED TFE............TOP OF FOOTING ELEVATION T.O............TOP OF T.O.S.........TOP OF SLAB, STEP, OR STEEL T.O.SLAB...TOP OF SLAB TPE...........TOP OF PIER ELEVATION TWE...........TOP OF WALL ELEVATION UNO............UNLESS NOTED OTHERWISE V................VERTICAL VERT..........VERTICAL VIF.............VERIFY IN FIELD W.P............WORKING POINT WS.............WALL STEP W/..............WITH XB..............X-BRACE STRUCTURAL ABBREVIATIONS OCCUPANCY CLASSIFICATION......................EDUCATIONAL OCCUPANCY CATEGORY............................... III MINIMUM DESIGN LOADS PER BUILDING CODE OF NEW YORK STATE (NYSBC) 2015. LOAD COMBINATIONS............NYSBC 1605.2 OR 1605.3 MIN FLOOR LIVE LOADS (1607): UNIFORM CONCENTRATED ASSEMBLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STAIRS AND EXITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ROOF LIVE LOADS (1607.11.2): MIN ROOF LIVE LOAD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ROOF SNOW LOAD (1608): GROUND SNOW LOAD Pg. . . . . . . . . . . . . . . . . . . . . . . . . . . FLAT-ROOF SNOW LOAD Pf . . . . . . . . . . . . . . . . . . . . . . . . SLOPED ROOF FACTOR . . . . . . . . . . . . . . . . . . . . . . . . SNOW EXOSURE FACTOR Ce. . . . . . . . . . . . . . . . . . . . . . SNOW IMPORTANCE FACTOR Is. . . . . . . . . . . . . . . . . . . . THERMAL FACTOR Ct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SNOW DRIFT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UNBALANCED SNOW LOADS . . . . . . . . . . . . . . . . . . . . . . WIND LOAD (1609): BASIC DESIGN WIND SPEED. . . . . . . . . . . . . . . . . . . . . . . WIND IMPORTANCE FACTOR Iw . . . . . . . . . . . . . . . . . . . . BUILDING CATEGORY (ASCE 1-1) . . . . . . . . . . . . . . . . . . WIND EXPOSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INTERNAL PRESSURE COEFF . . . . . . . . . . . . . . . . . . . . . EXT COMP & CLADDING PRESSURE (1609.1.1 & ASCE 7-10) BUILDING DESIGN LOADS AREA 10 SF 100 SF 500 SF NEGATIVE ZONE 4 NEGATIVE ZONE 5 POSITIVE ZONES 4 & 5 -35.1 -43.2 32.4 -30.4 -33.7 27.7 -27.0 -27.0 24.3 SURFACE PRESSURE (PSF)WALL 100 PSF 100 PSF 300# 20 PSF 40 PSF 34 PSF 1.0 1.0 1.1 1.1 PER ASCE 7-10 PER ASCE 7-10 115 MPH (2015 CODE BASIS) 1.0 III B +/-0.18 EARTHQUAKE DESIGN DATA (1613): SEISMIC IMPORTANCE FACTOR (I) . . . . . . . . . . . . . . . . . OCCUPANCY CATEGORY. . . . . . . . . . . . . . . . . . . . . . . . . SPECTRAL RESPONSE ACCELERATION, Ss . . . . . . . SPECTRAL RESPONSE ACCELERATION, SI . . . . . . SPECTRAL RESPONSE COEF SDS . . . . . . . . . . . . . . . . SPECTRAL RESPONCE COEF SDI . . . . . . . . . . . . . . . . . SITE CLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SEISMIC DESIGN CETEGORY . . . . . . . . . . . . . . . . . . . . . BASIC SEISMIC -FORCE -RESISTING SYSTEM ORDINARY REINFORCED CONCRETE MOMENT FRAMES DESIGN BASE SHEAR PER ASCE 7 V = .056W SEISMIC RESPONSE COEFFICIENT Cs. . . . . . . . . . . . . . RESPONSE MODIFICATION FACTOR R. . . . . . . . . . . . . . . . . . ANALYSIS PROCEDURE. . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 III 12.6 %g 5.6 %g 0.134 0.09 D B 0.056 3 EQUIVALENT LATERAL FORCE (ASCE) NOTES: 1.THE ABOVE TABLE APPLIES TO GRADE 60 DEFORMED BARS. 2.CLEAR SPACING BETWEEN BARS SHALL BE NOT LESS THAN 2 BAR DIAMETERS. IF CLEAR BAR SPACING IS LESS THAN 2 BAR DIAMETERS, MULTIPLY THE ABOVE LAP LENGTHS BY 1.5. 3.FOR EPOXY COATED BARS, MULTIPLY THE ABOVE LAP LENGTHS BY 1.2 FOR CLEAR SPACING BETWEEN BARS GREATER THAN 6 BAR DIAMETERS, OR 1.5 IF CLEAR SPACING IS LESS THAN 6 BAR DIAMETERS. FOR WALLS, SLABS, FOOTINGS & BEAMS CONCRETE STRENGTH, PSI BAR SIZE #3 #4 #5 #6 #7 #8 #9 #10 FOR PIERS & COLUMNS 3000 3500 4000 4500 5000 ALL CONCRETE 1'-11" 2'-4" 2'-10" 4'-1" 4'-8" 5'-3" 6'-11" 1'-5" 1'-9" 2'-2" 2'-7" 3'-9" 4'-4" 4'-10" 5'-6" 1'-4" 1'-8" 2'-0" 2'-5" 3'-7" 4'-1" 4'-7" 5'-2" 1'-3" 1'-7" 1'-11" 2'-4" 3'-4" 3'-10" 4'-4" 4'-10" 1'-2" 1'-6" 1'-10" 2'-2" 3'-2" 3'-7" 4'-1" 4'-7" 1'-1" 1'-3" 1'-7" 1'-11" 2'-2" 2'-6" 2'-10" 3'-2" 1'-0" CONCRETE REINFORCING SPLICE SCHEDULE GENERAL NOTES 1. CONTRACTOR SHALL VERIFY ALL CONDITIONS, DIMENSIONS, AND ELEVATIONS SHOWN AND IMMEDIATELY REPORT ANY DISCREPANCIES OR OMISSIONS TO THE ARCHITECT PRIOR TO CONSTRUCTION OR FABRICATION. 2.SECTIONS AND DETAILS ARE CONTINUOUS AND TYPICAL UNLESS NOTED OTHERWISE. 3.CONTRACTOR SHALL DETERMINE EXACT LOCATION OF EXISTING UTILITIES BEFORE COMMENCING WORK. CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR DAMAGES WHICH MIGHT BE OCCASIONED BY FAILURE TO EXACTLY LOCATED AND PRESERVE EXISTING UTILITIES. 4.PROVIDE BARRICADES, WARNING SIGNALS, WARNING LIGHTS AND SIMILAR ITEMS AS REQUIRED AND MAINTAIN THROUGHOUT CONSTRUCTION. CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY AND PROTECTION. 5.CONTRACTOR SHALL COORDINATE ALL CONCRETE, EARTHWORK, AND CONCRETE MASONRY WORK WITH THE INSPECTION AND TESTING AGENCY RETAINED BY THE OWNER. 1.THE STRUCTURAL STEEL FRAME AS DESIGNED IS A NON-SELF-SUPPORTING STEEL FRAME. COORDINATE THE ERECTION WITH THE INSTALLATION OF OTHER BUILDING ELEMENTS REQUIRED FOR THE STRUCTURE'S STABILITY. THESE ELEMENTS INCLUDE SLABS, METAL DECK, MASONRY WALLS, AND CONCRETE WALLS. PROVIDE AND MAINTAIN TEMPORARY SHORING AND BRACING UNTIL THESE OTHER BUILDING ELEMENTS ARE COMPLETELY INSTALLED AND CURED. 2.STRUCTURAL STEEL WIDE-FLANGE SECTIONS SHALL COMPLY WITH ASTM A572 OR ASTM A992 (Fy=50 KSI). 3.STRUCTURAL STEEL TUBE SECTIONS SHALL COMPLY WITH ASTM A500, (Fy=46 KSI). 4.ALL OTHER STRUCTURAL SHAPES SHALL COMPLY WITH ASTM A 36 (Fy=36 KSI). 5.SHOP CONNECTIONS SHALL BE 3/4" DIAMETER ASTM F3125 GRADE A325 OR A490 HIGH STRENGTH BOLTED OR WELDED. (UNLESS OTHERWISED NOTED) 6.FIELD CONNECTIONS SHALL BE 3/4" DIAMETER ASTM F3125 GRADE A325 OR A490 HIGH STRENGTH BOLTED OR WELDED UNLESS OTHERWISE NOTED. FIELD BOLTED CONNECTIONS SHALL BE SHEAR/BEARING CONNECTIONS UNLESS OTHERWISE NOTED ON THE DRAWINGS. SHEAR BEARING CONNECTIONS SHALL BE INSTALLED TO THE SNUG TIGHT CONDITION. 8.STEEL FLOOR AND ROOF DECK SHALL BE MANUFACTURED TO THE SPECIFICATIONS OF THE STEEL DECK INSTITUTE. SEE THE PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS. 9.THE ANCHOR BOLT PLANS AND STRUCTURAL STEEL ERECTION DRAWINGS SHALL BE SUBMITTED AND REVIEWED PRIOR TO SUBMITTING FABRICATION DETAIL DRAWINGS, JOIST DRAWINGS OR DECK DRAWINGS. 10.SEE DRAWINGS AND SPECIFICATIONS FOR STEEL FINISH REQUIREMENTS. STRUCTURAL STEEL NOTES Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 GENERAL NOTES AND SCHEDULESS0.01 Project Number: 18.007 No.Description Date Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 SCHEDULE OF SPECIALINSPECTIONSS0.02 Project Number: 18.007 No.Description Date 216 SF Meeting Room 01 B05B EXTERIOR 5" SLAB ON GRADE WITH 6x6-W4xW4 WWR. T/SLAB = -13'-6" (VIF) 5" SLAB ON GRADE WITH 6x6-W4xW4 WWR. T/SLAB = -8'-3 1/4" (VIF) DOWN [-4'-0"][-6'-0"][-8'-0"][-10'-0"][-13'-0"][-16'-0"] [-16'-0"] 6' - 6"12' - 10"8' - 2"3' - 6"3' - 6"3' - 10"TOP/FTGSTEPSTOP/FTGSTEPSTOP/FTGSTEPSTOP/FTGSTEPSFND WALL 8" CONC FND WALL1' - 0" CONC6' - 6"FTG2' - 0" CONCT/WALL = -8" T/WALL = +12" 4' - 6"1' - 0"4' - 9"7' - 6"FND WALL 1' - 0" CONC FTG 2' - 0" CONC K J H 7 VERIFY EXISTENCE OF EXISTING FOOTING DRAIN AND REROUTE AROUND NEW RETAINING WALL STEP FOOTING TO MATCH EXISTING FOOTING OPENING 5' - 0"24' - 8"2" WALL 8" FND DOWEL FOOTING AND FOUNDATION WALL INTO EXISTING FOUNDATION. MATCH REINFORCED SIZE AND SPACING SEE DETAIL 2/S300. TYPICAL 2' - 0"T/WALL = -13'-11" DOWEL FOOTING AND FOUNDATION WALL INTO ADJACENT FOUNDATION. MATCH REINFORCED SIZE AND SPACING SEE DETAIL 2/S300. TYPICAL 1 S4.01 5 S4.00 2 S4.01 7 S3.00 6' - 4" 7 RISERS @ 7" 5' - 6" (6 TREADS @ 11")4' - 4" 16 RISERS @ 7" 13' - 9" (15 TREADS @ 11") 3 S1.00 5" STRUCTURAL SLAB W/ #4 @ 12" O.C EACH WAY 2"x3/16" GALVANIZED STEEL BAR GRATING BY McNICHOLS OR EQUAL W/ 1/2"x1/2" GALV. WIRE MESH SCREENING BELOW L2x2x1/8" GALV PERIMETER ANGLES 4' - 0"16' - 0"16' - 0" S1.00 4 POST POST2' - 0"18" DIA CONCRETE PIER T/PIER = +6" 4 S3.00 2'-0"x2'-0"x12" CONCRETE SPREAD FOOTINGPOST POST 6"6"4"6"6"POST2' - 9 1/4"5' - 0" SEE ENLARGED FOUNDATION PLAN FOR MORE INFO [-3'-0"] EQ EQ EXIST COL EXIST COL EXIST COL 2% SLOPE AREA DRAIN SEE PLBG DRWG AREA DRAIN SEE PLBG DRWG 5 S1.00 FOUNDATION SYMBOLS KEY: INDICATES LOCATION OF CONTRACTION JOINTS. SEE TYPICAL SLAB DETAIL. INDICATES FOUNDATION WALL STRIP FOOTING INDICATES SPREAD FOOTING & CONCRETE PIER. INDICATES TYP CONC FND WALL INDICATES TYP SHELF IN CONCRETE FOUNDATION WALL PX FX (XXX'-XX") (XXX'-X") INDICATES PIER TYPE. INDICATES TOP OF PIER ELEVATION. INDICATES SPREAD FOOTING TYPE. INDICATES TOP OF SPREAD FOOTING ELELVATION. [+/-0'-0"] INDICATES TOP/FTG ELEVATION FROM DATUM.[-3'-0"][-4'-0"]TOP/FTG ELEVATOIN (HIGH SIDE) TOP/FTG ELEVATION (LOW SIDE) INDICATES ELEVATION ELEVATION SCCJ INDICATES GRADE ELEVATIONXXXX.XX' 408 SF Mech Workshop B05H EQ 7' - 0" EQ AHU-1 WT = 2500 LBS.W6X25W6X25L6X6X1/2L6X6X1/2L6X6X1/2 L6X6X1/22" NOM. DIAMETER STEEL PIPE. 40 GA. TYPICAL 4 LOCATIONS.21' - 9"(+8'-6")(+8'-6")6 G.3 G.5 EQEQEQEQFACE OFCFMF STUDSPOSTFACE OF CFMF STUDS FACE OF CFMF STUDS FACE OF CFMF STUDS FACE OF CFMF STUDS EQEQEQEQPOST6 S4.01 TYP4' - 2 11/16"5' - 1"FACE OF CFMF STUDS 7 SEE PLAN CVR2"5" STRUCTURAL SLAB W/ #4 @ 12" O.C. EACH WAY BAR GRATING SEE PLAN L2x2x1/8" GALV PERIMETER ANGLES ANCHORED TO CONC. WITH 1/2" Ø x 4" LONG SHEARSTUD ANCHORS ON 4 SIDES (2 EA. SIDE) T/EXIST FIRST FLOOR SLAB ELEV = 0'-0" WALL REINFORCING SEE 7/S3.00 SEE PLAN FND WALL K 7 FND WALL 1' - 0" CONC FTG 2' - 0" CONC FND WALL1' - 0" CONC6' - 6"FTG2' - 0" CONC[-7'-6"] T/WALL = +12" T/WALL = +12" EXISTING EXTERIOR WALL 5" SLAB ON GRADE WITH 6x6-W4xW4 WWR. T/SLAB = -4'-6" (VIF) BELOW AREA DRAIN, SEE PLBG DRWG GENERAL NOTES 1. CONTRACTOR SHALL VERIFY ALL CONDITIONS, DIMENSIONS, AND ELEVATIONS SHOWN AND IMMEDIATELY REPORT ANY DISCREPANCIES OR OMISSIONS TO THE ARCHITECT PRIOR TO CONSTRUCTION OR FABRICATION. 2.SECTIONS AND DETAILS ARE CONTINUOUS AND TYPICAL UNLESS NOTED OTHERWISE. 3.CONTRACTOR SHALL DETERMINE EXACT LOCATION OF EXISTING UTILITIES BEFORE COMMENCING WORK. CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR DAMAGES WHICH MIGHT BE OCCASIONED BY FAILURE TO EXACTLY LOCATED AND PRESERVE EXISTING UTILITIES. 4.PROVIDE BARRICADES, WARNING SIGNALS, WARNING LIGHTS AND SIMILAR ITEMS AS REQUIRED AND MAINTAIN THROUGHOUT CONSTRUCTION. CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY AND PROTECTION. 5.CONTRACTOR SHALL COORDINATE ALL CONCRETE, EARTHWORK, AND CONCRETE MASONRY WORK WITH THE INSPECTION AND TESTING AGENCY RETAINED BY THE OWNER. #4 x 2'-0" REBAR DOWELS @ 2' 0.C. EPOXY ANCHOR INTO EXG FND. WALL -6" EMBEDMENT. TYP STAIR TREAD FFE SEE PLAN EXG FND WALL Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 FOUNDATION PLANS1.00 Project Number: 18.007 3/8" = 1'-0"1 PARTIAL FOUNDATION PLAN 3/8" = 1'-0"2 AHU EQUIPMENT SUPPORT PLATFORM 1" = 1'-0"3 FOUNDATION SECTION AT AREAWAY 3/8" = 1'-0"4 ENLARGED PARTIAL FOUNDATION PLAN AT AREAWAY NOTES 1. DATUM ELEVATION IS AT TOP OF BASEMENT SLAB ELEVATION. 2. ELEVATIONS NOTED ARE WITH RESPECT TO DATUM ELEVATION. NOTES 1. DATUM ELEVATION IS AT TOP OF FIRST FLOOR ELEVATION = 0'-0". 2. ELEVATION NOTED ARE WITH RESPECT TO DATUM ELEVATION. 3. SEE S3.00 FOR TYPICAL SLAB ON GRADE DETAILS. NOTES 1. DATUM ELEVATION IS AT TOP OF FIRST FLOOR ELEVATION = 0'-0". 2. ELEVATION NOTED ARE WITH RESPECT TO DATUM ELEVATION. 3. SEE S3.00 FOR TYPICAL SLAB ON GRADE DETAILS. No.Description Date 3/4" = 1'-0"5 STAIR DOWEL TO EXG DETAIL UP 1 S4.00 L4X4X7/16L4X4X7/16 L2X2X1/4L2x2x1/4L2x2x1/4L2x2x1/4L2x2x1/4L2x2x1/43" DIA SCHED 40 PIPE (TYPICAL 4 LOCN'S) 3" DIA SCHED 40 PIPE. HD GALV. (TYPICAL 4 LOCATIONS) C12x25 1" x 3/16" GALV STEEL BAR GRATING TREADS. 21 TREADS AT = 19' - 3" K J 4' - 10 15/16"L2x2x1/410' - 1 1/2"EQEQEQEQC12x25C12x25 C12x251" x 3/16" GALV STEEL BAR GRATING. TO BE ADA COMPLIANT. BASIS OF DESIGN IS GCM SERIES PRESS-LOCKED BAR GRATING BY McNICHOLS 7' - 1 3/4" 2 S4.00 3 S4.00 4 S4.00 POSTPOSTPOST3"4' - 2 3/4"5' - 3"POST POST 4 3/4" 4 3/4"4 3/4"3 S4.01 16' - 0" (VIF) 5' - 0"1' - 6" L4x4x7/16"(-1")(+4")L4x4x7/16"(-1") L4X4X7/16 (-1") (-1") C12x25 (+4")(+4")K J 7 DEMO EXISTING CONCRETE LANDING DEMO EXISTING STAIR RAILINGS DEMO (4) STEEL POSTS AND ASSOCIATED FOOTINGS DEMO EXISTING STEEL STAIR STRINGERS DEMO EXISTING STEEL PAN CONCRETE STAIRS S1.01 3 4' - 0" ±6' - 4" ± (VIF)18' - 0" ± (VIF) GENERAL NOTES 1. CONTRACTOR SHALL VERIFY ALL CONDITIONS, DIMENSIONS, AND ELEVATIONS SHOWN AND IMMEDIATELY REPORT ANY DISCREPANCIES OR OMISSIONS TO THE ARCHITECT PRIOR TO CONSTRUCTION OR FABRICATION. 2.SECTIONS AND DETAILS ARE CONTINUOUS AND TYPICAL UNLESS NOTED OTHERWISE. 3.CONTRACTOR SHALL DETERMINE EXACT LOCATION OF EXISTING UTILITIES BEFORE COMMENCING WORK. CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR DAMAGES WHICH MIGHT BE OCCASIONED BY FAILURE TO EXACTLY LOCATED AND PRESERVE EXISTING UTILITIES. 4.PROVIDE BARRICADES, WARNING SIGNALS, WARNING LIGHTS AND SIMILAR ITEMS AS REQUIRED AND MAINTAIN THROUGHOUT CONSTRUCTION. CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY AND PROTECTION. 5.CONTRACTOR SHALL COORDINATE ALL CONCRETE, EARTHWORK, AND CONCRETE MASONRY WORK WITH THE INSPECTION AND TESTING AGENCY RETAINED BY THE OWNER. Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 SECOND FLOOR FRAMING PLANS1.01 Project Number: 18.007 1/2" = 1'-0"1 EXTERIOR STAIR FRAMING PLAN 1/2" = 1'-0"2 EXISTING STAIR DEMOLITION PLAN 1" = 1'-0"3 EXISTING EXTERIOR STAIR NOTE 1. DATUM ELEVATION IS AT TOP OF SECOND FLOOR LANDING ELEVATION +12'-4" 2. ALL ELEVATIONS NOTED ARE WITH RESPECT TO DATUM ELEVATION. 3. ALL EXTERIOR STEEL HOT DIP GALVANIZED. No.Description Date REINF W/ 6x6-W4xW4 WWF UNO. SUPPORT MESH ON WIRE BASKETS OR CONCRETE BRICK. SUPPORT MESH AND PULL-UP DURING PLACEMENT SO THAT MESH IS LOCATED BETWEEN 1" AND 2 1/2" FROM TOP OF SLAB. UNDISTURBED EARTH OR COMPACTED SELECT STRUCTURAL FILL AS REQD TO BRING TO PROPER GRADE SEE SPEC FOR CURING AND FINISH REQUIREMENT SEE PLANDMIN6"COMPACTED SLAB SUBBASE 5"1' - 7" EXG FND WALL NEW FND WALL CONTINUOUS WATERSTOP AT JOINT #5 REINFORCING ROD ANCHORED W/ EPOXY ADHESIVE @ 12" OC AT WALL CENTER #4 x 2'-0" REBAR DOWELS @ 2' 0.C. EPOXY ANCHOR IN EXG SLAB -6" EMBEDMENT. EXISTING SLAB ON GRADE TYP FLR SLAB SEE DETAIL FFE SEE PLAN EXG FND WALL DEMO EXISTING WALL FOR NEW OPENING SEE PLANSCHEDDEPTHSEE FTGPLAN SEE PLAN FTG SIZE - SEE FND SEE PIER PLAN MATCH VERT REINF (3) #4 EACH WAY BOTTOM MATT.COVER3"EXTEND DWLS DOWN TO FTG REINF AS SHOWN SCHEDULESEE LAP/EMBED1' - 0" 2" COVER SEE BASE PLATE DETAIL 6/S3.00 SEE PLAN SEE PIER PLAN DETAIL SEE PLAN FOR PIER SIZE T/PIER 8 S3.00 SEE PLAN T/FOOTING ALL STEEL HOT DIP GALVANIZED 1" CHAMFER 12" STAIR STRINGER SEE ARCH 3/4" DIAMETER EXPANSION ANCHOR. EMBED 4" MIN THICKEN SLAB TO 12" FOR FULL WIDTH OF STAIR BASE REINF W/ 6x6-W4xW4 WWF STAIR PIPE COLUMN 8"x8"x3/4" BASE PLATE 1/4" LEVELING PLATE. 3/4" NON-SHRINK GROUT -MINIMUM (4) 3/4"Ø x 8" POST INSTALLED ANCHOR BOLTS (HILTI KWICK- BOLT 3 HDG OR EQUAL) TYP 1 1/2" EQ EQ 10"7"TYP1 1/2"EQEQCOL COLPOST EMBEDMENT4" MINALL EXTERIOR STEEL HOT DIP GALVANIZED 1" CHAMFER #4@18" O.C VERT UNDISTURBED COMPACTED SUBGRADE (2) #5 CONT. REINFORCED EXTERIOR SLAB ON GRADE OR CONCRETE STAIR. 6" RAILING POST SLEEVES CAST INTO TOP OF RETAINING WALL. T/WALL SEE TOP OF FTG 2' - 0"4"2' - 0"SEE PLAN 3' - 0"2' - 0"#4@18" OC HOOK REST ON BOTTOM MATT #6 @ 8" OC HORIZ. #4 @ 18" OC VERT. FOUNDATION PLAN NEW STEEL RAILING. #4@18" O.C HORIZ 8" #8@ 8" OC HOOK REST ON BOTTOM MATT 2' - 0" 1' - 0" NON-WOVEN GEOTEXTILE FILTER FABRIC (TENCATE MIRAFI 140N OR EQUIV.) 4" DIA ASTM D2129 PERFORATED PVC DRAIN PIPE (PLACE HOLES DOWN) DRAINAGE PANEL ALONG FACE OF RETAINING WALL ADJACENT TO AREAWAY. WATERPROOFING MEMBRANE EQ EQ TYP3" CVR#4 BENT DOWELS AT 12" O.C. 2' 2' COVER 2" WATERSTOP WALL 1' - 0"FINISHED GRADE (3) #3 CIRCULAR TIES AT EACH GUARD POST T/SLAB @ BASEMENT ALL STEEL HOT DIP GALVANIZED TYP 2" CVR #3 CIRCULAR TIES @ 12" O.C. (5) #5 VERT. REINFORCING SEE PLAN Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 FOUNDATION DETAILSS3.00 Project Number: 18.007 1 1/2" = 1'-0"1 TYPICAL SLAB ON GRADE DETAIL 3/4" = 1'-0"2 TYP FNDN WALL DOWEL TO EXG DET 3/4" = 1'-0"3 SLAB EDGE @ EXISTING DETAIL 1/2" = 1'-0"4 TYP PIER/ FTG DETAIL 1 1/2" = 1'-0"5 STRINGER CONNECTION AT SLAB 1 1/2" = 1'-0"6 COLUMN BASE PLATE 3/4" = 1'-0"7 RETAINING WALL DETAIL 1 1/2" = 1'-0"8 PIER PLAN DETAIL No.Description Date FIRST FLOOR 0' - 0" SECOND FLOOR LANDING 12' - 4" K J 19' - 3 1/2"12' - 4"3' - 6"2' - 10"4"1 1/2" DIAMETER SCHED. 40 HORIZONTAL RAILS 1 1/2" DIAMETER SCHED. 40 POSTS 6' - 9 1/2" 1 1/2" DIAMETER SCHED. 40 HANDRAIL. 4 S4.01 SIML2x2x1/4" AT LANDING PERIMETER L4x4 STAIR HEADER 1'-0" HANDRAIL EXTENSION 6' - 5 3/16"6' - 5 3/16"6' - 5 3/16" S3.00 5 1" BAR GRATING TREADS TYP 11" TYP 1"TYP6 3/4"1 /4" STEEL PLATE RISER. TYPICAL 1" STEEL BAR GRATING LANDING 3' - 6"2' - 10"FIRST FLOOR 0' - 0" SECOND FLOOR LANDING 12' - 4" 19' - 3"6' - 11 1/2" 4 S4.01 SIM 1'-0" HANDRAIL EXTENSION 1 1/2" DIAMETER SCHED. 40 HORIZONTAL RAILS 1 1/2" DIAMETER SCHED. 40 POSTS 1 1/2" DIAMETER SCHED. 40 HANDRAIL. L2x2x1/4" AT LANDING PERIMETERL4x4 STAIR HEADER 1" BAR GRATING TREADS 1 /4" STEEL PLATE RISER. TYPICAL 1" STEEL BAR GRATING LANDING TYP 1" TYP 11"TYP6 3/4"C12 CHANNEL LANDING SUPPORT POST 6' - 5"6' - 5"6' - 5" S3.00 5 2 7 / 8 "3' - 6"2' - 10"SECOND FLOOR LANDING 12' - 4" 1 S4.00 10' - 1 13/16"9"CAP HANDRAIL END AND TERMINATE WITHIN 1/2" OF WALL POST AND LANDING EDGE 1/2" GAP AT GUARD 4 S4.01 SIM 1" STEEL BAR GRATING LANDING LANDING SUPPORT POST L4x4 LANDING SUPPORT ANGLE L2x2 LANDING SUPPORT PERIMETER ANGLES 4' - 11 5/8"4' - 11 5/8"3' - 6"2' - 10"SECOND FLOOR LANDING 12' - 4" 5' - 8 1/4"3' - 6"4 S4.01 SIM CAP HANDRAIL END AND TERMINATE POST AND LANDING EDGE 1/2" MAX GAP AT GUARD 1" STEEL BAR GRATING LANDING LANDING SUPPORT POST L4x4 LANDING SUPPORT ANGLE L2x2 LANDING SUPPORT PERIMETER ANGLES 2' - 10"1' - 0" FIRST FLOOR 0' - 0" 77 2' - 1 1/4"1' - 0"3' - 2 3/4"3' - 6"EXTERIOR STAIR COLUMN 1 1/2" OD STEEL PIPE RAIL 1 1/2" OD STEEL PIPE 1 1/2" OD STEEL PIPE RAILS AT 6" O.C. 1 1/2" OD STEEL PIPE BOTTOM RAIL BASE PLATE ASSEMBLY. SEE FOUNDATION DETAILS. GUARD POST GROUTED INTO POST SLEEVES CAST INTO CONCRETE WALL. SEE RETAINING WALL SECTION. Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 STAIR SECTIONS 1S4.00 Project Number: 18.007 1/2" = 1'-0"1 Section 4 1/2" = 1'-0"2 Section 12 1/2" = 1'-0"3 Section 6 1/2" = 1'-0"4 Section 7 1/2" = 1'-0"5 Section 10 No.Description Date FIRST FLOOR 0' - 0" J H 6"3' - 6"6' - 0 13/16"6' - 0 13/16"6' - 0 13/16"5' - 11 1/16"3 1/2" REMOVABLE GUARD 5' - 11 1/16"6" 1 1/2" DIAMETER SCHED. 40 HORIZONTAL RAILS AT 5" O.C. 1 1/2" DIAMETER SCHED. 40 POSTS EXTERIOR STAIR COLUMN BASE PLATE ASSEMBLY. SEE FOUNDATION DETAILS. CAST IN SLEEVES ALLOW FOR FUTURE TEMPORARY RAILING REMOVAL GUARD POST GROUTED INTO POST SLEEVES CAST INTO CONCRETE WALL. SEE RETAINING WALL SECTION. FIRST FLOOR 0' - 0" T/BASEMENT SLAB -13' - 0" J H 2'-0"x2'-0" #4 BENT DOWELS @ 1'-0" O.C. #3 NOSE BARS AT EACH TREAD #4 @ 12 O.C E.W. #3 NOSE BARS AT EACH TREAD 5" REINFORCED SLAB ON GRADE 5" REINFORCED SLAB ON GRADE #4 @ 12 O.C E.W. 1 1/2" DIAMETER HANDRAIL AT BOTH SIDES OF STAIR 8"8"2'-0"x2'-0" #4 BENT DOWELS @ 1'-0" O.C. 2'-0"x2'-0" #4 BENT DOWELS @ 1'-0" O.C. #4 @ 12 O.C E.W. #4 @ 12 O.C E.W. SEE PLAN 1' - 0"1' - 0"SEE PLAN BOT - STAIR -13' - 5" 8 " 3 " TYP TYP 11" TYP 3/4"TYP7"5 S4.01 TYP EA. SIDE OF STAIR EXTENSION 1' - 0" HANDRAIL FLOOR DRAIN SEE MECH DRWG 2' - 10"EXTERIOR DOOR GAP 1/2" MAX STEEL BAR GRATING SEE PLAN SEE PLAN T/LANDING LANDING EDGE ANGLE FFE 2nd FLR 5 7/16"5 7/16"5 7/16"5 7/16"5 7/16"5 7/16"5 7/16"3' - 6"2 7/8"2' - 7 1/8"1 1/2"4"1 1/2" DIA SCHED 40 HANDRAIL 1 1/2" DIA SCHED 40 HORIZONTAL RAILS 1 1/2" DIA SCHED 40 VERTICAL POSTS 3/4" DIA ROUND STEEL BAR @ 3'-6" O.C. MAX 1" STEEL BAR GRATING 3/16" T/LANDING OR TREAD SEE PLAN 1/4" 1 1/2"4"EXISTING CONCRETE WALL 1 1/2" NOMINAL SCHED 40 PIPE CONTINUOUS HANDRAIL WELD AND GRIND SMOOTH 1/4" THICK 3" DIA. ROUND STEEL PLATE @ 3'-6" O.C. MAX WITH COUNTERSUNK SELF TAPPING METAL SCREWS NOSING2'-10" ABOVE3/4" ROUND STEEL BAR @ 3'-6" O.C. MAX ALL STEEL HOT DIP GALVANIZED TOP/ STAIR TREAD SEE PLAN 1/2" NON-SHRINK GROUT 1/2"x3"x9" BASE PLATE W/(2) 1/2"Ø x EXPANSION ANCHOR SPACE 6" APART. 4" EMBED POST, BASE PLATE AND ANCHORS 2"1 1/2"1"2"1"T/STEEL SEE PLAN STEEL WIDE FLANGE BEAM (2) 3/4" ASTM A3125 GRADE A325 HIGH STRENGTH BOLTS 2" NOM. POST SEE PLAN EXISTING 5" SLAB ON GRADE (VIF) T/EXIST SLAB VIF 3/16 4" Sheet Number 45 LEWIS STREET BINGHAMTON, NY 13901 607.217.7013 www.L2studioarch.com Owner:Project Address:Professional Seal: Revisions NOTICE:It is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter this Drawing in any way. If alterations are made to this Drawing, when bearing the seal of an architect, the altering party shall affix their own professional seal to his/her revisions, and add the notation "altered by" followed by his/her signature and the date of such alteration, and a specific written description of the alteration(s) made. FINAL BID SETSheet TitleConsultant:Elwyn Palmer& CONSULTING ENGINEERS, PLLC 213 East Seneca Street Ithaca, New York 14850 www.ElwynPalmer.com 607.272.5060 Carpenter Hall B05 Systems Engineering Lab CodeComplianceCornell University313 Campus RdIthaca, NY 14850Date: 3/5/2019 STAIR SECTIONS 2S4.01 Project Number: 18.007 1/2" = 1'-0"1 RETAINING WALL RAILING ELEVATION 1/2" = 1'-0"2 CONCRETE STAIR ELEVATION 1" = 1'-0"3 LANDING EDGE AT ENTRY DETAIL 1" = 1'-0"4 STAIR RAILING DETAIL 3" = 1'-0"5 TYPICAL HANDRAIL BRACKET DETAIL 1 1/2" = 1'-0"6 TYPICAL INTERIOR FRAME CONNECTION DETAIL No.Description Date