HomeMy WebLinkAbouts0011 DESIGN DATA NOTES 2 GENERAL: DESIGN PROVISIONS . 2017 NEW YORK STATE UNIFORM CODE (NYSUC) INCORPORATING THE 2015 INTERNATIONAL BUILDING CODE (IBC) RISK CATEGORY _ II TERRAIN/EXPOSURE CATEGORY B CODE COMPLIANCE FOR EXISTING STRUCTURES: DESIGN PROVISIONS 2017 NEW YORK STATE UNIFORM CODE (NYSUC) INCORPORATING THE 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC) COMPLIANCE METHOD (IEBC) - WORK AREA CLASSIFICATION OF WORK (IEBC) REPAIR, LEVEL 2 ALTERATION EXISTING STRUCTURAL ELEMENTS RESISTING LATERAL LOADS ARE NO LESS CONFORMING TO THE PROVISIONS OF THE 2017 NYSUC WITH RESPECT TO EARTHQUAKE DESIGN THAN THEY WERE PRIOR TO THIS WORK. THE BUILDING IS IN CONFORMANCE WITH THE LAW IN EXISTENCE AT THE TIME THE BUILDING WAS CONSTRUCTED. THEREFORE LATERAL LOADS HAVE NOT BEEN EVALUATED FOR THIS STRUCTURE. 3. LIVE LOADS: PORCH FRAMING HAS BEEN DESIGNED TO SUPPORT 100 PSF UNIFORMLY DISTRIBUTED LIVE LOAD. 4. DEAD LOADS: 5. SEISMIC LOADS: SITE CLASS: D (ASSUMED) 5 psf SHORT -PERIOD DESIGN ACCELERATION (Sds): ONE -SECOND DESIGN ACCELERATION (Sd1): 0.090 SHORT PERIOD MAPPED SPECTRAL RESPONSE (Ss): 0.126 ONE -SECOND MAPPED SPECTRAL RESPONSE (S1): 0.056 SEISMIC DESIGN CATEGORY: B IMPORTANCE FACTOR (le): 1.0 0.134 6. WIND LOADS: ULTIMATE WIND SPEED (3 SECOND GUST) (Vult): 115 mph NOMINAL WIND SPEED (3 SECOND GUST) (Vasd): 90 mph TOPOGRAPHIC FACTOR (Kzt): 1.0 ENCLOSURE CLASSIFICATION (PORCH FRAMING): OPEN 9. SOIL PRESSURE: PRESUMPTIVE SOIL BEARING PRESSURE: 2,000 PSF ON UNDISTURBED MATERIAL OR COMPACTED STRUCTURAL FILL. 10. STRUCTURAL MATERIAL STRENGTHS: STRUCTURAL AND MISCELLANEOUS STEEL: ROLLED STEEL C, S, M, MC, AND HP SHAPES - ASTM A 36 OR ASTM A 572, GRADE 50 ROLLED STEEL PLATES, BARS, AND ANGLES - ASTM A 36 OR ASTM A 572, GRADE 50 CONCRETE: FOOTINGS, MISCELLANEOUS f'c = 3,000 psi RETAINING WALLS, BASEMENT WALLS, FOUNDATION WALLS, PIERS f'c = 4,000 psi EXTERIOR SLABS ON GRADE - fc = 4,500 psi (SEE SPECIFICATIONS FOR SLUMP AND AIR ENTRAINMENT) REINFORCING STEEL FOR CONCRETE: ASTM A 615, GRADE 60 DIMENSION LUMBER: STRUCTURAL FRAMING NO, 1/NO. 2 OR BETTER, SPRUCE -PINE -FIR (SPF) Fb = 875 psi Fc = 425 psi (PERPENDICULAR TO GRAIN) E = 1,400;000 psi Fc = 1,150 psi (PARALLEL TO GRAIN) GENERAL NOTES 1. DIMENSIONS TO, OF, AND IN EXISTING STRUCTURE SHALL BE VERIFIED IN FIELD BY CONTRACTOR. 2. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY DISCREPANCIES IN DIMENSIONS BETWEEN EXISTING CONDITIONS AND/OR ARCHITECTURAL DRAWINGS AND THE STRUCTURAL DRAWINGS. 3. DO NOT CHANGE SIZE OR SPACING OF STRUCTURAL ELEMENTS. 4, DETAILS SHOWN ARE TYPICAL; SIMILAR DETAILS APPLY TO SIMILAR CONDITIONS UNLESS OTHERWISE INDICATED. 5. THE NOTES ON THIS DRAWING ARE TYPICAL UNLESS OTHERWISE INDICATED. 6. CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING OF PROPOSED DEVIATIONS OR SUBSTITUTIONS FROM DIMENSIONS, MATERIALS, OR EQUIPMENT SHOWN ON THE DRAWINGS AND MAKE ONLY THOSE DEVIATIONS OR SUBSTITUTIONS ACCEPTED BY ENGINEER. 7. CONTRACTOR SHALL DETERMINE EXACT LOCATIONS OF EXISTING UTILITIES BEFORE COMMENCING WORK. CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR DAMAGES WHICH MIGHT OCCUR AS A RESULT OF FAILING TO EXACTLY LOCATE AND PRESERVE EXISTING UTILITIES, 8. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION SAFETY. FOUNDATION NOTES 1. BEAR FOOTINGS ON FIRM UNDISTURBED SOIL OR COMPACTED STRUCTURAL FILL. 2. FOOTINGS HAVE BEEN DESIGNED FOR A SOIL BEARING PRESSURE OF 2,000 psf. 3. SOIL BEARING SURFACES PREVIOUSLY ACCEPTED BY GEOTECHNICAL ENGINEER WHICH ARE ALLOWED TO BECOME SATURATED, FROZEN, OR DISTURBED SHALL BE REWORKED TO SATISFACTION OF GEOTECHNICAL ENGINEER. 4. WHERE FOOTING ELEVATIONS ARE LOWERED DUE TO SOIL CONDITIONS, LOWER ADJACENT FOOTINGS IN ELEVATION IN ORDER THAT RATIO OF CLEAR DISTANCE BETWEEN NEAREST EDGE OF FOOTINGS TO DIFFERENCE IN ELEVATION BETWEEN BOTTOMS OF FOOTINGS SHALL NOT EXCEED 2H:1V. 5. FOUNDATION PREPARATION: REFER TO SPECIFICATIONS FOR "EXCAVATION, BACKFILL, AND COMPACTION (BUILDING AREA)." 6. DO NOT PLACE FOOTINGS IN WATER OR ON FROZEN GROUND. 7. DO NOT ALLOW GROUND BENEATH FOOTINGS TO FREEZE. 8. CENTER FOOTINGS UNDER WALLS, PIERS, AND COLUMNS UNLESS NOTED OTHERWISE. 9. WHERE REQUIRED, STEP NEW FOOTINGS UP OR DOWN IN RATIO OF TWO HORIZONTALS TO ONE VERTICAL TO JOIN EXISTING FOOTINGS. 10. CONCRETE WALLS SHALL ATTAIN A MINIMUM STRENGTH OF 70% f'c BEFORE PLACING BACKFILL AGAINST THEM. 11. WALLS THAT ARE TO BE BACKFILLED ON ONE SIDE ONLY MAY BE BACKFILLED UP TO 3 FEET ABOVE THE TOP OF FOOTING AFTER WALLS ATTAIN MINIMUM STRENGTH OF 70% fc. REMAINING BACKFILL MAY NOT BE PLACED UNTIL TOP SLAB IS IN PLACE, SLAB ATTAINS MINIMUM STRENGTH OF 70% fc, AND WALLS ATTAIN MINIMUM STRENGTH 100% f'c. 3 4 5 CAST -IN-PLACE CONCRETE NOTES (FOUNDATION) 1. REINFORCE CONCRETE ELEMENTS INCLUDING FOOTINGS, WALLS, PIERS, AND SLABS. REINFORCEMENT SHOWN PERTAINS TO TYPICAL CONDITIONS. 2, LAP SPLICE CONCRETE REINFORCEMENT AS INDICATED IN THE CONCRETE REINFORCEMENT LAP SPLICE SCHEDULE, UNLESS NOTED OTHERWISE, 3. LAP CONTINUOUS FOOTING AND HORIZONTAL WALL REINFORCEMENT WITH A CLASS B LAP SPLICE UNLESS NOTED OTHERWISE. 4. PROVIDE CORNER BARS IN FOOTINGS, THE SAME SIZE AND NUMBER AS CONTINUOUS REINFORCEMENT. PROVIDE CLASS B LAP SPLICE WITH MAIN REINFORCEMENT, BUT NO LESS THAN 2'-0". 5. PLACE TRANSVERSE REINFORCEMENT IN CONTINUOUS FOOTINGS WHERE SHOWN IN BOTTOM LAYER. 6. CAST STEPPED FOOTINGS MONOLITHICALLY. 7. DOWEL CONCRETE WALLS AND PIERS INTO FOOTINGS WITH DOWELS THE SAME SIZE AND SPACING AS VERTICAL REINFORCEMENT. EXTEND DOWELS TO WITHIN 3 INCHES OF BOTTOM OF FOOTING, TERMINATED WITH A.C.I. STANDARD 90 DEGREE HOOK. PROVIDE CLASS B LAP SPLICE WITH VERTICAL REINFORCEMENT UNLESS NOTED OTHERWISE. 8. AT INTERSECTIONS OF CONCRETE WALLS, PROVIDE CORNER BARS IN OUTER LAYER THE SAME SIZE AND SPACING AS HORIZONTAL REINFORCEMENT AND PROVIDE A CLASS B LAP SPLICE WITH MAIN REINFORCEMENT, BUT NOT LESS THAN 2'-0". AT "T" INTERSECTIONS, PROVIDE CORNER BARS FROM EACH LAYER IN INTERSECTING WALL TO OUTER LAYER OF THROUGH WALL. 9. PROVIDE KEYS IN CONCRETE WALLS AND FOOTINGS AT VERTICAL CONSTRUCTION JOINTS UNLESS NOTED OTHERWISE. KEYS SHALL BE 1 1/2 INCHES DEEP AND THE WIDTH OF THE KEY SHALL BE ONE- THIRD THE WALL THICKNESS AND CENTERED WITHIN THE WALL. 10. VERIFY SIZE AND LOCATION OF MECHANICAL OPENINGS. 11. CONDUIT AND UTILITY PENETRATIONS THROUGH STRUCTURAL SLABS AND WALLS SHALL BE SLEEVED OR CHASED. NO CORE -DRILLING OF SLABS OR WALLS IS PERMITTED. PENETRATIONS ARE NOT PERMITTED THROUGH PIERS. 12. MINIMUM BAR DEVELOPMENT LENGTH EQUALS CLASS A LAP LENGTH. 13. CHAMFER EXPOSED CONCRETE CORNERS AND EDGES 3/4 INCH UNLESS NOTED OTHERWISE. 14. CONCRETE COVER FOR REINFORCEMENT SHALL BE AS INDICATED IN THE CONCRETE COVER SCHEDULE. CONCRETE REINFORCEMENT LAP SPLICE SCHEDULE BAR LAP LENGTHS, UNCOATED BARS CLEAR COVER NOT LESS THAN TWO TIMES BAR DIAMETER CLEAR SPACING NOT LESS THAN FOUR TIMES BAR DIAMETER BAR SIZE MINIMUM CLEAR COVER (INCH) MINIMUM SPACING CENTER/CENTER (INCH) CLASS B LAP NOT A TOP BAR (INCH) CLASS B LAP TOP BAR (INCH) CLASS A LAP NOT A TOP BAR (INCH) CLASS A LAP TOP BAR (INCH) #4 1 2 1/2 22 28 17 22 #5 1 1/4 3 1/8 27 35 21 27 #6 1 1/2 3 3/4 32 42 25 32 BAR LAP LENGTHS, UNCOATED BARS CLEAR COVER NOT LESS THAN BAR DIAMETER CLEAR SPACING NOT LESS THAN TWO TIMES BAR DIAMETER BAR SIZE MINIMUM CLEAR COVER (INCH) MINIMUM SPACING CENTER/CENTER (INCH) CLASS B LAP NOT A TOP BAR (INCH) CLASS B LAP TOP BAR (INCH) CLASS A LAP NOT A TOP BAR (INCH) CLASS A LAP TOP BAR (INCH) #4 1/2 1 1/2 29 37 22 29 #5 5/8 17/8 36 46 28 36 #6 3/4 2 1/4 43 56 33 43 NOTES FOR SCHEDULE: 1. TOP BARS ARE DEFINED AS HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 12 INCHES OF FRESH CONCRETE IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. 2. USE CLASS B LAP SPLICES, UNLESS NOTED OTHERWISE. 3. FOR COVER AND SPACING DIMENSIONS WHICH ARE IN BETWEEN THE TABULATED VALUES, DO NOT INTERPOLATE, INSTEAD USE THE LONGER LAP LENGTH. SEE CONCRETE COVER SCHEDULE. 4. CALCULATE CENTER TO CENTER SPACING DIMENSIONS OF BARS AT SPLICE LOCATIONS. 5. FOR EPDXY COATED BARS MODIFY THE TABULATED LAP LENGTHS AS FOLLOWS: A. FOR TOP BARS AND BARS WHICH ARE NOT A TOP BAR WITH A CLEAR COVER OF GREATER THAN OR EQUAL TO 3 TIMES THE BAR DIAMETER AND CLEAR SPACING GREATER THAN OR EQUAL TO 6 TIMES THE BAR DIAMETER, MULTIPLY THE TABULATED LENGTH BY 1.2. B. FOR BARS WHICH ARE NOT A TOP BAR, WITH A CLEAR COVER LESS THAN 3 TIMES THE BAR DIAMETER AND CLEAR SPACING LESS THAN 6 TIMES THE BAR DIAMETER, MULTIPLY THE TABULATED LENGTH BY 1.5. C. FOR TOP BARS, WITH A CLEAR COVER LESS THAN 3 TIMES THE BAR DIAMETER AND CLEAR SPACING LESS THAN 6 TIMES THE BAR DIAMETER, MULTIPLY THE TABULATED LENGTH FOR TOP BARS BY 1.3. CONCRETE COVER SCHEDULE LOCATION COVER FOOTINGS POURED AGAINST EARTH: 3" SURFACE EXPOSED TO WEATHER OR EARTH (INCLUDING SURFACES OF FOUDATION WALLS COVERED WITH WATERPROOFING MEMBRANE AND/OR INSULATION): BARS LARGER THAN #5 2" #5 BARS OR SMALLER 1 1/2" BETWEEN BARS AND EMBEDDED ITEMS: IN CONCRETE ELEMENTS EXPOSED TO WEATHER OR EARTH 1 1/2" IN CONCRETE ELEMENTS NOT EXPOSED TO WEATHER OR EARTH 3/4" 6 7 SLAB ON GRADE NOTES 1. SUBGRADE BELOW SLAB ON GRADE SHALL BE REVIEWED AND ACCEPTED BY GEOTECHNICAL ENGINEER BEFORE CONCRETE SLAB PLACEMENT. 2. PROVIDE PROTECTION FROM PRECIPITATION AND EXCESSIVE COLD TEMPERATURES FOR THE SLAB SUBBASE PRIOR TO SLAB -ON -GRADE PLACEMENT. SUBBASE MUST BE DRY AND NOT FROZEN AT THE TIME OF SLAB PLACEMENT. 3. DO NOT PLACE SLABS ON FROZEN GROUND. IF SUBGRADE OR SUBBASE ARE FROZEN AFTER PREPARATION. THEY SHALL BE THAWED THEN RECOMPACTED AND RETESTED FOR COMPACTION PRIOR TO SLAB PLACEMENT, AT THE EXPENSE OF THE CONTRACTOR. 4. PROVIDE PROTECTION FOR THE SLAB ON GRADE FROM DIRECT EXPOSURE TO THE SUN, WIND, PRECIPITATION, AND EXCESSIVE COLD OR HOT TEMPERATURES STARTING DURING PLACEMENT AND LASTING UNTIL THE END OF THE CURING PERIOD. DO NOT ALLOW GROUND BENEATH SLABS TO FREEZE. 5. PRIOR TO SLAB PLACEMENT, SUBMIT FOR INFORMATION ONLY A WRITTEN PROTECTION PROGRAM FOR THE SLAB SUBBASE AND SLAB ON GRADE. 6. PROVIDE A SQUARE EDGE FORM JOINT FOR CONSTRUCTION JOINTS AND A SAW -CUT JOINT FOR CONTRACTION JOINTS IN SLABS ON GRADE. CONTINUE 50 PERCENT OF SLAB REINFORCEMENT THROUGH CONSTRUCTION AND CONTRACTION JOINTS. 7. REINFORCE SLABS AS NOTED ON DRAWINGS. AT PERIMETER OF SLABS, LOCATE REINFORCING 3 INCHES FROM SLAB EDGES. 8. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. STRUCTURAL STEEL NOTES 1. DO NOT BEGIN STEEL ERECTION UNTIL SUPPORTING CONCRETE OBTAINS 75 PERCENT OF THE MATERIAL STRENGTHS NOTED IN DESIGN DATA NOTES. 2. DO NOT PLACE HOLES THROUGH STRUCTURAL STEEL MEMBERS EXCEPT AS SHOWN AND DETAILED ON STRUCTURAL DRAWINGS, 3. PROVIDE HOT DIP GALVANIZED FASTENERS FOR GALVANIZED FRAMING CONNECTIONS AND STAINLESS STEEL FASTENERS FOR STAINLESS STEEL FRAMING CONNECTIONS. 4. GALVANIZING WHERE NOTED IN THE DRAWINGS SHALL BE HOT -DIP GALVANIZING IN ACCORDANCE WITH ASTM A123, UNLESS NOTED OTHERWISE. WOOD FRAMING NOTES 1, ACCURATELY CUT, FIT, AND SOLIDLY FASTEN MEMBERS TO PROVIDE PLUMB, LEVEL, TRUE, AND RIGID WORK. NAILING NOT INDICATED ON DRAWINGS SHALL BE IN ACCORDANCE WITH "FASTENING SCHEDULE" CONTAINED IN THE 2015 INTERNATIONAL BUILDING CODE TABLE 2304.10.1. 3. FOR BOLTED CONNECTIONS, DRILL HOLES 1/16 INCH LARGER IN DIAMETER THAN THE BOLTS BEING USED. PROVIDE WASHERS AND NUTS UNDER BOLT HEADS IN CONTACT WITH WOOD. 4. ANCHOR SILL PLATE OF EXTERIOR WALLS TO FOUNDATION WALLS WITH 1/2 INCH -DIAMETER BY 1 - FOOT -LONG WITH 2 -INCH GALV HOOK ANCHOR RODS WITH NUTS AND WASHERS. LOCATE ANCHOR RODS 12 INCHES MAXIMUM FROM EACH END AND 6 FEET MAXIMUM ON CENTER. (MINIMUM OF TWO ANCHOR RODS IN EACH SILL PIECE.) EMBED ANCHOR RODS A MINIMUM OF 9 INCHES IN CAST IN PLACE CONCRETE. 5. INSTALL JOISTS WITH CROWN EDGE UP AND SUPPORT ENDS OF EACH MEMBER WITH NOT LESS THAN 1 1/2 INCHES OF BEARING ON WOOD OR METAL OR 3 INCHES ON MASONRY. 6. JOISTS SHALL BE SUPPORTED LATERALLY AT THE ENDS AND AT EACH SUPPORT BY 2 -INCHES -BY - FULL -DEPTH SOLID BLOCKING (UNLESS DETAILED OTHERWISE) EXCEPT WHERE THE ENDS ARE ANCHORED TO A BEAM, HEADER, BAND JOIST, OR ARE HELD IN POSITION BY HANGERS. 7, BRIDGING OR 2 -INCHES -BY -FULL -DEPTH SOLID BLOCKING SHALL BE INSTALLED IN FLOOR JOISTS AT INTERVALS NOT EXCEEDING 8 FEET. 8. LAP MEMBERS FRAMING FROM OPPOSITE SIDES OF BEAMS, GIRDERS, OR LOAD-BEARING WALLS NOT LESS THAN 4 INCHES OR SECURELY TIE OPPOSING MEMBERS TOGETHER. INSTALL 2 -INCHES - BY -FULL -DEPTH SOLID BLOCKING AT SUPPORTS. 9. DO NOT NOTCH JOISTS IN THE MIDDLE THIRD OF THE SPAN. LIMIT NOTCHES ON THE TOP OR BOTTOM FACE OF THE JOIST TO A MAXIMUM DEPTH OF 1/6 OF THE DEPTH OF THE MEMBER AND MAXIMUM LENGTH OF 1/3 THE DEPTH OF THE MEMBER UNLESS ACCEPTANCE OF ENGINEER IS OBTAINED. NO OVERCUTS WILL BE PERMITTED. 10, DO NOT BORE HOLES CLOSER THAN 2 INCHES FROM TOP OR BOTTOM OF JOISTS. LIMIT DIAMETER OF HOLES TO 1/3 THE DEPTH OF THE MEMBER. REVIEW BORE HOLE LOCATIONS WITH ENGINEER BEFORE PROCEEDING. 11. USE PRESSURE -TREATED WOOD FOR ELEMENTS EXPOSED TO WEATHER; IN CONTACT WITH SOIL, WATER, MASONRY, CONCRETE; OR FOR WOOD JOISTS AND STRUCTURAL FLOORING DIRECTLY ABOVE SOIL WHEN THE BOTTOM ELEVATION IS LESS THAN 18 INCHES ABOVE SOIL AND FOR WOOD BEAMS WHEN THE BOTTOM ELEVATION IS LESS THAN 12 INCHES ABOVE SOIL. 12, SIMPSON STRONG -TIE FRAMING CONNECTORS ARE INDICATED ON THE DRAWINGS. EQUIVALENT CONNECTORS FROM OTHER MANUFACTURERS MAY BE SUBMITTED FOR REVIEW, 13. PROVIDE G185 HOT -DIPPED GALVANIZED COATING MEETING THE REQUIREMENTS OF ASTM A 653 FOR METAL FRAMING CONNECTORS IN CONTACT WITH PRESSURE TREATED LUMBER. FASTENERS USED WITH THESE CONNECTORS SHALL BE HOT DIPPED GALVANIZED TO COMPLY WITH ASTM A 153. Z -MAX FINISH BY SIMPSON STRONG -TIE OR ACCEPTED EQUIVALENT. 8 9 STRUCTURAL OBSERVATION NOTES 10 1. THE REGISTERED DESIGN PROFESSIONAL WILL MAKE VISITS TO THE SITE AT APPROPRIATE INTERVALS FOR THE PURPOSE OF OBSERVING THE CONSTRUCTION FOR GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS. THE FOLLOWING LIST INCLUDES SOME APPROPRIATE TIMES FOR VISITING THE SITE. THE CONTRACTOR SHALL NOTIFY THE REGISTERED DESIGN PROFESSIONAL AT LEAST 48 HOURS PRIOR TO PERFORMING THESE ACTIVITIES SO THAT SITE VISITS CAN BE SCHEDULED. • INITIAL PLACEMENT OF REINFORCING BARS FOR FOOTINGS, FOUNDATION WALLS, RETAINING WALLS, AND PIERS (AFTER EXCAVATION AND PRIOR TO THE CLOSING OF FORMS). • PLACEMENT OF REINFORCING BARS FOR STRUCTURAL CONCRETE SLAB. • INITIAL FRAMING LAYOUT AND CONNECTIONS FOR WOOD CONSTRUCTION • COMPLETION OF THE STRUCTURAL SYSTEM. • OTHER TIMES AS REQUIRED DUE TO FIELD CONDITIONS OR SPECIAL CONSTRUCTION TYPES. 2. THE REGISTERED DESIGN PROFESSIONAL MAY VISIT THE SITE AT TIMES OTHER THAN THOSE LISTED IN NOTE 1. 3. THE REGISTERED DESIGN PROFESSIONAL WILL PREPARE A FIELD OBSERVATION REPORT FOR EACH SITE VISIT MADE TO OBSERVE CONSTRUCTION. PART II OF EACH REPORT IS FOR CONTRACTOR VERIFICATION AND IS MANDATORY. PART II MUST BE COMPLETED (SIGNED BY THE CONTRACTOR VERIFYING THAT THE REQUIRED ACTION WAS TAKEN AND LISTING THE DATE COMPLETED) AND RETURNED TO THE ENGINEER IN A TIMELY MANNER. SPECIAL INSPECTION NOTES 1. THE OWNER WILL ENGAGE THE SERVICES OF A QUALIFIED SPECIAL INSPECTOR FOR THIS PROJECT, WHO WILL PROVIDE AND/OR COORDINATE INSPECTION AND TESTING REQUIREMENTS AS NECESSARY IN ACCORDANCE WITH THE PROVISIONS OF CHAPTER 17 OF THE BCNYS. 2. THE REGISTERED DESIGN PROFESSIONAL HAS PREPARED A STATEMENT OF SPECIAL INSPECTIONS, WHICH INCLUDES SPECIFICATION 014533, AND THE SCHEDULE OF SPECIAL INSPECTIONS. THESE DOCUMENTS WILL BE SUBMITTED WITH THE CONTRACT DOCUMENTS AND THE APPLICATION FOR BUILDING PERMIT TO THE CODE ENFORCEMENT OFFICIAL. 3. SPECIAL INSPECTIONS AND TESTING SHALL BE CONTINUOUS OR PERIODIC DURING THE PERFORMANCE OF THE WORK, AS NOTED. 4. THE CONTRACTOR SHALL HOLD A PRE -CONSTRUCTION MEETING WITH THE REGISTERED DESIGN PROFESSIONAL, SPECIAL INSPECTOR, TESTING AGENCY, AND AFFECTED SUB -CONTRACTORS TO REVIEW THE REQUIRED SPECIAL INSPECTION AND TESTING REQUIREMENTS FOR THE PROJECT. THE CONTRACTOR SHALL DISTRIBUTE CONSTRUCTION SCHEDULES TO EACH ATTENDEE, 5. THE SPECIAL INSPECTOR SHALL SUBMIT INTERIM REPORTS AND, AT THE COMPLETION OF SPECIAL INSPECTIONS, A FINAL STATEMENT OF SPECIAL INSPECTIONS. REPORTS SHALL BE STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER. 6. THE SPECIAL INSPECTOR SHALL NOTIFY THE CONTRACTOR IMMEDIATELY OF DISCREPANCIES. SUBSEQUENT REPORTS SHALL NOTE WHEN AND HOW DEFICIENCIES WERE CORRECTED. THE SPECIAL INSPECTOR SHALL NOTIFY THE REGISTERED DESIGN PROFESSIONAL AND THE CODE ENFORCEMENT OFFICIAL OF DISCREPANCIES WHICH HAVE NOT BEEN CORRECTED. 7. THE CONTRACTOR SHALL COOPERATE WITH THE SPECIAL INSPECTOR INCLUDING ADVANCE NOTIFICATION OF REQUIRED INSPECTION OR TEST, INCIDENTAL LABOR. AND SAFE ACCESS TO THE WORK AREAS, AND ACCESS TO CONTRACT DOCUMENTS SO THAT INSPECTIONS AND TESTING MAY BE PERFORMED WITHOUT HINDRANCE. 8. THE SPECIAL INSPECTION PROGRAM SHALL IN NO WAY RELIEVE THE CONTRACTOR OF THE OBLIGATION TO PERFORM THE WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS OR FROM IMPLEMENTING AN EFFECTIVE QUALITY CONTROL PROGRAM. 9. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. ABBREVIATIONS LEGEND ADJ ADJACENT L ANGLE APPROX APPROXIMATE ARCH ARCHITECT ARCHITECTURAL B/ BOTTOM OF BLDG BUILDING BRG BEARING BP BASE PLATE CANT CANTILEVER CJ CONTROL, CONTRACTION, CONSTRUCTION JOINT CMU CONCRETE MASONRY UNIT(S) CONC CONCRETE CONT CONTINUOUS COL COLUMN CFMF COLD -FORMED METAL FRAMING COORDINATE DIAMETER DIMENSION DOWN DITTO DRAWING EACH EACH FACE EXPANSION JOINT ELECTRICAL ELEVATION ELEVATOR ENGINEER EMBEDDED EQUAL EQUIPMENT EACH SIDE EACH WAY EXISTING COORD DIA DIM DN do DWG EA EF EJ ELEC EL ELEV ENGR EMBD EQ EQUIP ES EW EXIST EXT EOD EOS FD FDN FTG GA GALV HSS HORI EXTERIOR EDGE OF DECK EDGE OF SLAB FLOOR DRAIN FOUNDATION PSF FOOTING GAUGE PSI GALVANIZED HOLLOW STEEL SECTION PCF PE PERP PLF Z HORIZONTAL HI HP HVAC INFO INT INV K LG LLH LLV LOC LW LVL HIGH HIGH POINT HEATING/VENTILATING/ INFORMATION INTERIOR INVERT KIPS LONG LONG LEG HORIZONTAL LONG LEG VERTICAL LOCATION LIGHT WEIGHT LAMINATED VENEER LUMBER LO LOW MANUF MANUFACTURER MAX MAXIMUM MECH MECHANICAL MIN MISC MO NA NIC NOM NW OC OD MINIMUM MISCELLANEOUS MASONRY OPENING NOT APPLICABLE NOT IN CONTRACT NOMINAL NORMAL WEIGHT ON CENTER OUTSIDE DIAMETER OPNG OPENING OPP OPPOSITE PAF POWDER ACTUATED FASTENER PC PSL R RD RDP REQD REINF REV RO SIM SPA STD SF SS STL SQ T/ TYP UNO PROFESSIONAL ENGINEER PERPENDICULAR POUNDS PER LINEAL FOOT POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH POUNDS PER CUBIC FOOT PRECAST PARALLEL STRAND LUMBER RADIUS ROOF DRAIN REGISTERED DESIGN PROFESSIONAL REQUIRED REINFORCING OR REINFORCED REVISION OR REVISED ROUGH OPENING SIMILAR SPACE STANDARD SQUARE FEET STAINLESS STEEL STEEL SQUARE TOP OF TYPICAL UNLESS NOTED OTHERWISE VERT VERTICAL VIF VERIFY IN FIELD W/ WITH WP WORK POINT WWR WELDED WIRE REINFORCEMENT WCJ WALL CONTROL OR CONSTRUCTION JOINT RYAN BIGGS CLARK DAVIS 4592 JORDAN ROAD SKANEATELES FALLS, NY 13153 p 315.685,4732 f 315.685.4753 www.ryanbiggs.com E U 0 0 c 0 0 U a) is 0 • • 0 CO 0 LL co C to N 0- _1_0= E U (0 a) 2 criP CE! haca, New York 14850 DATE: 14 December 2018 PROJECT: 1711 E D C 13 OTHER: DRAWN BY: CGM GENERAL NOTES S00 1 A 1 2 4 5 6 7 8 10