HomeMy WebLinkAboutBuilding 3 - Underground Piping CertificationCONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR UNDERGROUND PIPING
Procedure
Upon completion of work, inspection and tests shall be made by contractor's representative and witnessed by an owners representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is
understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure
to comply with approving authority's requirements or local ordinances.
PROPERTY NAME Jp��V� ( DATE_i/�, / o A /a
PROPERTY ADDRESS Lo
( �- r
ACCEPTEDa'?APPROVIN UTTHHO,ITY(')NAMES
ADDRESS PLANS ({ f
! I,v -eN/Ri� "5.�1�(EJ
INSTALLATION CONFORMS TO ACCEPTED PLANS ,YES ❑ NO
NO
EQUIPMENT USED IS APPROVED
IF NO, STATE DEVIATIONS:
HAS THE PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION -ETC'ES ❑ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT.
IF NO, EXPLAIN
INSTRUCTIONS
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS 4n"FE—S ❑ NO
BEEN LEFT ON THE PREMISES.
IF NO, EXPLAIN
LOCATION SUPPLIES BLDGS3A CO (4{Up /I ,6 ,1 ��,� C✓
PIPE TYPES AND CLASS „. 1 LP,�. JOIt�/T�ly a S ( TYl�D� i
PIPE CONFORMS TO AW I STANDARD 2-YtS ❑l NO
UNDERGROUND FITTINGS CONFORM TO _A;p," k STANDARD 5-Y S ❑ NO
PIPES IF NO, EXPLAINAND I
,��
JOINTS JOINTS NEEDING ANCHORAGECLAMPED, STRAPPED, OR BLOCKED IN CS ❑ NO
ACCORDANCE WITH STANDARD
IF NO, EXPLAIN N,ft
FLUSHING: Flow the required rate until water is clear as Indicated by no collection of foreign material in burlap bags at outlets
such as hydrants and blow -offs. Flush at flows not less than 400 gpm (16141/min) for 44nch pipe, 600 gpm (2271 I/min) for 5-
inch pipe, 900 gpm (2839 1/min) for 6-Inch pipe, 1600 gpm (3785 Vmin) for 8-Inch pipe, 2440 gpm (56781/min) for 10-inch pipe,
and 3520 gpm (7570 I/min) for 12-Inch pipe. When supply cannot produce stipulated flow rates, obtain maximum available.
TEST HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.8 bars) for two hours or 50 psi (3.4 bars) above
DESCRIPTION static pressure in excess of 150 psi, (10.3 bars) for two hours.
LEAKAGE: New pipe laid with rubber gasketed joints shall, if the workmanship is satisfactory, have little or no leakage at the
joints. The amount of leakage at the joints shall not exceed 2 qts per hr (1.89 I/h) per 100 joints irrespective of pipe diameter.
The leakage shall be distributed over all joints. If such leakage occurs at a few joints the Installation shall be considered
unsatisfactory and necessary repairs made. The amount of allowable leakage specified above may be increased by 1 fi oz Per
in. valve diameter per hour (30 mU26 mm/h) for each metal seated valve isolating the test section. If dry barrel hydrants are
tested with the main valve open, so the hydrants are under pressure, an additional 6 oz/min leakage is permitted for each
Ed NW UNDERGROUND PIPING FLUSHED ACCORDING TO STANDARD El YES ❑ NO
BY: (COMPANY)
IF NO, EXPLAIN
HOV,FLUSHING FLOW WAS OBTAINED THROUGH WHAT TYPE OPEN�IN .
FLUSHING 2MUBLIC MAIN ❑ TANK OR RESERVOIR ❑ FIRE PUMP I ❑ HYDRANT BUTT 0 OPEN PIPE uu
TESTS
LEAD-INS FLUSHED ACCORDING TO�STANDARD OYES ❑ NO
BY: (COMPANY)
IF NO. EXPLAIN q,A P
HING
HO UBLIC MAIN F ❑ TANKSOR RE ERVOIR ❑ FIRE PUMP ( ❑ Y CONN TO FLANGE & SP GO OPENINOPEN PIP '" ~
HYDROSTATIC
ALL NEW UNDERGROUND PIPING HYDROSTATICALLY TESTED AT
TESTS
Z�_ PSI FOR 2 HOURS
TOTLL AMOUNT OF LEAKAGE MEASURED
LEAKAGE
GALS. OVER '!)„HOURS
TEST
ALLOWABLE LEAKAGE
GALS. OVER,_„ HOURS
NUMBER IJS ALLED
TYPE AND MAKE
ALL OPERATE SATISFACTORILY
HYDRANTS
�
❑YES ❑ NO
WATER CONTROL VALVES LEFT WIDE OPEN
21 S ❑ NO
CONTROL
IF NO, STATE REASON
VALVES
HOSE THREADS OF FIRE DEPARTMENT CONNECTIONS AND HYDRANTS INTERCHANGEABLE
WITH THOSE OF FIRE DEPARTMENT ANPWERING ALARM
ES El NO
DATE LEFT IN SERVICE
REMARKS
NAME OF INSTALLING CONTRACTOR
TESTS WITNESSED BY
SIGNATURES
FOR PR ERTY OWNER (SIGNED
TITLE �-
DATE /� _ _ l p� t(/�
l
!TTwV•`^.-
FNST�ALLING ONTTOR (SIGNED)
DAD7f���_//�;�(/�/(/(//
��--
-'
C1PM
44
� r
ADDITIONAL EXPLANATIONS AND NOTES