Loading...
HomeMy WebLinkAboutBuilding 3 - Fire Pump Startup Report Date: 5/13/2024 To: Petcosky Fire Protection 421 Commerce Rd Binghamton NY 13850 Attention: Joe Betkavsky Subject: Fire Pump Certification Location: Cathrine Commons South Bldg #3 210 College Ave Ithaca, NY Gentlemen: The following report covers field-testing of existing Patterson Fire Pump at subject location, on 5/09/2024 Manufacturer: Patterson Pumps Model: 6X5X17SSC Serial No: FPC000217638-01 Capacity: 1000 GPM Head: 75 PSI Speed: 1775 Horsepower: 60 HP Driver: WEG Model 0601803VP364TS Ser No: 1061666302 Controller: Firetrol FTA1930-AM60H-TSA SER No: FZ1260835 The fire pump installation, the suction supply piping and discharge piping, and the pump driver, and control panel were inspected and found to be acceptable. A flow test was conducted, assisted, and witnessed by the following: Ed Helinski, Gartner Equipment Co, Inc. (Patterson Rep) Dan Mahar, McPeak Co (Firetrol Rep) Joseph Betkavsky, Petcosky Fire Protection Brad Scott, Petcosky Fire Protection Owen Davis, Petcosky Fire Protection Chris Hamilton, Ithaca Fire Dept (Fire Marshal Inspector) TO: Petcosky Fire Protection Page 2 Timothy Bush, Schuler-Haas (Electrician) Kevin Jenkins, Schuler-Haas (Alarms) The fire pump and controller were further tested for (6) each “Automatic Start and stops”. The fire pump and controller were further tested for (7) each “Manual Start and Stops”. Controller was left in: Manual shut down mode. Controllers were left in the OFF position on. Jockey pump rotation was confirmed, and pressure was set in JP controller. The fire system, when placed in the “Automatic” mode of operation, will sequence with pressure switches/ transducer as follows: Fire Pump Pressure Switch: "Start" @ 155 PSIG "Stop" @ 165 PSIG MANUAL Shutdown only. Jockey Pump Pressure Switch: "Start" @ 165 PSIG "Stop" @ 175 PSIG The jockey pump and jockey pump controller were tested and found to be acceptable as to installation and performance. Manufacture: Grundfos Model: CR3-8 Controller: Firetrol FTA560F-AG011H Ser#: FZ1260837 Enclosed with this report are the field test data, the performance curve drawn from the field test data superimposed on the factory certified test curve, the factory certified test data and curve, the pump nameplate data, and the hydrostatic test certificate. Regards, Ed Helinski GARTNER EQUIPMENT COMPANY, INC. ELECTRIC DRIVEN FIRE PUMP FLOW TEST DATA NOZZLE SIZE AND NUMBER PITOT PRESSURE GPM DISCHARGE PRESSURE Suction Pressure NET PRESSURE NET FEET/HEAD SPEED RPM VOLTS AMPS 0 0 0 200 105 95 219’ 1795 212/210/211 79/74/78 1-3/4”-1 32 504 190 96 94 217’ 1787 212/211/211 121/120/125 1-3/4”-2 32 1008 150 74 76 176’ 1786 211/210/211 157/156/163 1-3/4”-3 30/30/34 1495 96 47 49 111’ 1783 211/210/211 165/165/171 Generator 1-3/4”-3 30/30/34 1495 96 47 49 111’ 1784 207/208/207 167/169/172 Location: Catherine Commons South Bldg #3 Ithaca, NY Date: 5/09/2024 Patterson Pump Model: Patterson Model 6X5X17SSC Ser# FPC000217638-01 Contractor: Petcosky Fire Protection 0 25 50 75 100 125 150 175 200 225 250 0 25 50 75 100 125 150 175 200 225 250 0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100 0 250 500 750 1000 1250 1500 1750 2000 Patterson Pump Company Serial No: FP-C000217638-1 Sold To: GARTNER EQUIPMENT Job: 423923 Pump Type:6X5X17SSC Test Driver:WESTINGHOUSE GPM:1000 Imp Pattern:C-10892 HP:150 Ft. Head:173 Imp Dia:14.375 Eff%:0.924 Rated RPM:1775 Vane Tips:.125 Test RPM:1780 Test Num:3 No. Stages:1 Test Type:Performance Test Date:Jan-30-2023 Certified By:_________________ Approved By:__________________ Witnessed By:_________________ F t . H e a d B H P E f f . % N P S H GPM Eff. %Ft. Head BHP NPSH CK   0 25 50 75 100 125 150 175 200 225 250 0 25 50 75 100 125 150 175 200 225 250 0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100 0 250 500 750 1000 1250 1500 1750 2000 Patterson Pump Company Serial No: FP-C000217638-1 Sold To: GARTNER EQUIPMENT Job: 423923 Pump Type:6X5X17SSC Test Driver:WESTINGHOUSE GPM:1000 Imp Pattern:C-10892 HP:150 Ft. Head:173 Imp Dia:14.375 Eff%:0.924 Rated RPM:1775 Vane Tips:.125 Test RPM:1780 Test Num:3 No. Stages:1 Test Type:Performance Test Date:Jan-30-2023 Certified By:_________________ Approved By:__________________ Witnessed By:_________________ F t . H e a d B H P E f f . % N P S H GPM Eff. %Ft. Head BHP NPSH CK   6X5X17SSCGARTNER EQUIPMENT 1000 C-10892FP-C000217638-1 173 423923 177514.375 .125 1 150 1,500.00, 0.00Positive Pressure Test 1780 112.45, 0.006" 112.21 WESTINGHOUSE 474B859G095.00 CK 4606.00 Jan-30-2023 1770.00 3 1.150.00 300PSI 0.924 1 WaterTemp PSI kWPSI 1 112.00 14.80 23.90 1,798.00 0.00 0.00 224.53 0.00 32.04 29.60 0.00 0.00 218.82 28.48 2 108.00 15.20 40.40 1,795.00 20.80 511.76 214.93 27.78 54.16 50.04 55.51 506.05 210.17 48.39 3 98.00 14.30 45.80 1,794.00 56.20 841.20 194.87 41.40 61.39 56.73 72.97 832.29 190.76 54.94 4 91.00 13.60 48.20 1,794.00 81.30 1,011.76 181.00 46.24 64.61 59.70 77.46 1,001.04 177.18 57.82 5 82.00 13.00 49.80 1,793.00 110.70 1,180.61 162.39 48.41 66.76 61.68 78.49 1,168.75 159.15 59.84 6 75.20 12.40 50.50 1,794.00 132.50 1,291.63 148.66 48.49 67.69 62.55 77.52 1,277.95 145.53 60.58 7 61.00 11.40 50.50 1,795.00 183.00 1,517.95 119.54 45.82 67.69 62.55 73.25 1,501.04 116.89 60.48 8 43.00 10.20 49.00 1,794.00 240.00 1,738.35 82.27 36.12 65.68 60.69 59.51 1,719.94 80.54 58.78 9 35.00 9.80 48.10 1,795.00 265.00 1,826.65 65.39 30.16 64.48 59.58 50.63 1,806.29 63.95 57.61 PATTERSON PUMP COMPANY RATING (Design)PUMP DATAORDER INFORMATION GPM:Pump Size & Type:Customer: FT HD:Impeller Pattern:Serial No: RPM (N2):Job: Impeller Diameter: Vane Tips: Stages: TEST DRIVER INFORMATION SECONDARY RATINGSTEST INFORMATION HP: GPM: RPM:Venturi Meter: FT HD: Venturi Constant: Manufacturer: Data Collected by :Discharge Dia: Serial No.: Volts: Test Date :Suction Dia: Amps: Test No.:Discharge Guage Elev.(Zd): S.F.:Suction Guage Elev. (Zs): Eff.(.00):Pressure Ga: Panel No.: Test Data Calculated Data Calculated Data at Rated Speed whp ehp bhp1 npumpNo bhp2Q2 (GPM) H2 (FT)H1 (FT)Q1 (GPM))Ps (Pd ( ) h (" H2O)N1 Comments: UL/FM RATING 60HP Electric Fire Pump Testing Fire pumps are a critical part of a fire protection system. Properly maintained and tested fire pumps will deliver countless years of worry-free performance. Two types of testing of fire pumps are needed: 1) Weekly / Monthly testing which is typically done by facility personnel. 2) Annual flow test which should be done by a sprinkler contractor. All maintenance and testing should be done in accordance with NFPA25 - Standard for inspection, testing and maintenance of water-based fire protection systems. Proper safety precautions must be taken for any potential hazards. The purpose of weekly fire pump inspection and test is to ensure the fire pump is in an operating condition free of physical damage and capable of providing continuous delivery for fire protection demands. In addition, the purpose of a weekly test is to detect deficiencies that may not be obvious by visual inspections. Steps to perform a weekly / monthly test This weekly “Churn Test” verifies the operational status of the fire pump and identifies deficiencies that may not be evident by visual examination. To prevent false alarms, notification first should be provided to the alarm monitoring company prior to and after completion of the weekly / monthly fire pump test. After testing verify that all the fire pump supervisory signals were received by the alarm monitoring facility. Weekly Inspection Procedure Check the power indicating light (green) on the controller and verify there is power to the pump Check to make sure there is adequate heat in the room not less than 40 degrees F, note temperature at 4’ above floor is not the same as 1’ to the floor, sensing lines are typically close to the floor so adequate heat is very important. Check to make sure pump suction and discharge OSY control valves are opened. Bypass valve (if installed) is open. Examine all fittings for leaks. Check to make sure the pump suction and discharge gauges are reading normal. Confirm system gauge at controller reads normal, confirm controller reads normal. If equipped - confirm transfer switch pilot light is illuminated. Confirm there are no power loss or phase reversal alarms. Confirm the isolation switch on transfer switch is closed. (Up position on disconnect handle of transfer switch). Step (1) Verify START and STOP pressure of jockey pump: Make sure jockey is in “Auto Position”; SLOWLY open the valve on the sensing line near the controller, thus dropping system pressure in the jockey pump sensing line. Jockey pump should cycle ON and OFF without the main fire pump activating. If you open the line too quickly you may start the fire pump. Once confirmed turn jockey pump controller to “OFF” position. Step (2) After completion of all inspections, start the fire pump automatically by slowly opening the sensing line valve near the main fire pump controller. After pump starts it should run for 10 minutes. Step (3) Record the pressure at which the pump started automatically, record the pump discharge pressure and suction pressure at the pump gauges. Step (4) Confirm the pump casing circulation relief valve is dumping a constant stream of water. This must always dump when the pump is running at churn to allow for cool water to enter the pump case. Step (5) Check and keep an eye on the pump packing glands to ensure proper tightness and adequate lubrication, when pump is off ideally 1-2 drops per a second. Note that over tightening the gland will cause extreme heat and wear; water should always be dripping from the packing glands. MAKE SURE THE DRAIN LINE BELOW THE GLAND IS FLOWING FREELY. Step (6) Horizontal pumps: check pump shaft, bearings, and packing for any sign of overheating, check for unusual noises or vibrations on all pumps. Step (7) If pump is equipped with a main relief valve confirm that it is working properly. After the 10-minute run period you should be able to push the STOP button on the fire pump controller. If the controller has a LED screen the run time will be visible, “If” for any reason when you stop the pump the pressure is not above the controller set point the fire pump will automatically come ON when you remove the stop signal. If pressure is satisfied the pump should not come back on unless pressure drops. Verify that both Jockey pump and fire pump controllers are left in the Automatic Mode. If for any reason abnormal operation or conditions are noted during weekly / monthly churn test, the pump should be shut down and left in the automatic start position until repairs are made, repairs should be made as soon as possible, pump shall be retested. Fire pump controllers with transfer switches To de-energize a main fire pump controller with a transfer switch. If you must shut power down, first pull-down transfer switch disconnect (B), then pull down utility switch disconnect (A). To re-energize a main fire pump controller with a transfer switch. First turn on main power (utility) disconnect switch (A), then turn on transfer switch disconnect (B). Failure to follow correct order will likely cause the generator to start or second utility to be powered. Any questions or concerns I can be reached at 315 -476-8321 Regards, Ed Helinski